Texon manufactures best-quality products through continuous R&D and perfect quality control.
Network Product
Core & RNC Network Enclosure
Basic racks for a RNC
Basic racks used for a Radio Network Controller (RNC)
Categories
OEM
standards
19 inch
Size (H X W X D)
2,000 X 600 x 600mm
Network enclosures used for base stations or smaller
Outdoor Enclosure : MMBS Dual Outdoor Enclosure
A FDD LTE DU cabinet that consists of a MMBS Battery Cabinet and Set installed with a high-capacity rectifier. Installed with a 19x23-inch system, in compliance with the Zone4 standard, and certified to UL.
Categories
ODM
User Space
16U
Size (H X W X D)
1800 X 700 x 850mm
Weight
314kg
Operating temperature
-40 ℃ to +50 ℃, full power
Relative Humidity
5 ~ 100%RH
Earthquake
GR-63-Core, Zone 4
Ingress Protection
IP55
Cooling Capacity
2,000W
Heater
PTC Type
Battery Backup Time
4 Hours ( 4 Strings@190Ah )
Smart Control Unit
Temp, Door/Lamp, Flood, Smoke Detector
Power distribution
-48VDC
DC power distribution with lighting protection
30kA, 8/20us (RRH) @normal
Power Consumption
9,300W@Typical
Rectifier(PDU)
AC/DC, 3U LLVD, BLVD, CSC, Battery MCB Included, AC Distribution 1P+N+PE
Outdoor Enclosure : MMBS Single Outdoor Enclosure
A cabinet capable of serving as a stand-alone that is installed with FDD LTE DU, a battery, and a rectifier as well. Installed with a 19x23-inch system, in compliance with the Zone4 standard, and certified to UL.
Categories
ODM
User Space
10U
Size (H X W X D)
1800 X 700 x 850mm
Weight
328kg(Without Battery)
Operating temperature
-40 ℃ to +50 ℃, full power
Relative Humidity
5 ~ 100%RH
Earthquake
GR-63-Core, Zone 4
Ingress Protection
IP55
Cooling Capacity
2,000W
Heater
PTC Type
Battery Backup Time
4 Hours ( 1 Strings@190Ah )
Smart Control Unit
Temp, Door/Lamp, Flood, Smoke Detector
Power distribution
-48VDC
DC power distribution with lighting protection
30kA, 8/20us (RRH) @normal
Power Consumption
9,300W@Typical
Rectifier(PDU)
AC/DC, 3U LLVD, BLVD, CSC, Battery MCB Included, AC Distribution 1P+N+PE
Cabinets exclusively used for communication system batteries that consist of a MMBS Battery Cabinet and Set. In compliance with the same standard.
Categories
ODM
Battery Space
4String
Size (H X W X D)
1800 X 700 x 925mm
Weight
284kg(Without Battery)
Operating temperature
-40 ℃ to +50 ℃, full power
Relative Humidity
5 ~ 100%RH
Earthquake
GR-63-Core, Zone 4
Ingress Protection
IP55
Cooling Capacity
650W
Heater
PTC Type
Battery Backup Time
4 Hours ( 4 Strings@190Ah )
Smart Control Unit
Temp, Door/Lamp, Flood, Smoke Detector
Power distribution
-48VDC
DC power distribution with lighting protection
30kA, 8/20us (RRH) @normal
Power Consumption
DC 150W@Typical, AC 1,800W@Typical
Outdoor Enclosure : TD-LTE Outdoor Enclosure
Installed with TDD LTE DU and a battery as well, capable of serving as a stand-alone, in compliance with the Zone4 standard, and certified to UL.
Categories
ODM
Size (H X W X D)
2,000 X 700 X 1120 mm
Operating temperature
-40 ℃ to +50 ℃, full power
Relative Humidity
5 ~ 100%RH
Earthquake
GR-63-Core, Zone 4
Ingress Protection
IP55
Cooling Capacity
1,620W
Heater
PTC Type
Smart Control Unit
Temp, Door/Lamp, Flood, Smoke Detector
Power distribution
-48VDC
DC power distribution with lighting protection
30kA, 8/20us (RRH) @normal
Rectifier(PDU)
AC/DC, 3U LLVD, BLVD, Battery MCB Included, AC Distribution 1P+N+PE
Power Consumption
9,300W@Typical
Outdoor Enclosure : LG U+ LTE Outdoor Enclosure
LTE outdoor cabinets only for LG U+
Categories
OEM
Size (H X W X D)
1,600 X 750 X 810 mm
Operating temperature
-40 ℃ to +50 ℃, full power
Relative Humidity
5 ~ 100%RH
Ingress Protection
IP55
Heater
PTC Type
Smart Control Unit
Temp, Door/Lamp, Flood, Smoke Detector
Outdoor Enclosure : G-SOC Power Outdoor Enclosure
A small-size cabinet only for DUs, comprised of the same-size battery cabinet and set. Decreases installation space with a stackable installation, and advantageous from the viewpoints of CAPEX and OPEX. It is possible to make a single cabinet (for a stand-alone service) with a 1-string battery according to a request.
Categories
ODM
Total Space
16U
User Space
10U
Size (H X W X D)
800 X 575 X 600mm
Operating temperature
-40℃ to +55℃
Relative Humidity
5 ~ 100%RH
Earthquake
GR-63-Core, Zone 4
Ingress Protection
IP55
Cooling Capacity
1,020W (DU 2)
Heater
PTC Type
Battery Backup Time
TBD ( 2 Strings@100Ah )
Smart Control Unit
Door Open(+Lamp), Temp
Power distribution
-48VDC
DC power distribution with lighting protection
20kA, 8/20us (RRH) @normal
Rectifier(PDU)
AC/DC, 3U LLVD, BLVD, Battery MCB Included, AC Distribution 3P+N+PE
A cabinet only for batteries comprised of a G-SOC Power Cabinet and Set. In compliance with the same standard. In compliance with the same standard.
Categories
ODM
Battery Space
Possible to provide max 100Ah and 2 Strings, Free Space 15U
Size (H X W X D)
800 X 575 X 600mm
Operating temperature
-40℃ to +55℃
Relative Humidity
5 ~ 100%RH
Earthquake
GR-63-Core, Zone 4
Ingress Protection
IP55
Heater
PTC Type
Battery Backup Time
TBD ( 2 Strings@100Ah )
Smart Control Unit
Door Open(+Lamp), Temp
Outdoor Enclosure : G-SOC SRU Outdoor Case
As one of the G-SOC products, a case with an external fan which can accommodate 3 RU systems.
Categories
ODM
User Space
265mm, Possible to install maximum 3 RUs
Size (H X W X D)
400 X 600 X 600mm
Earthquake
GR-63-Core, Zone 4
Outdoor Enclosure : Mini-Power Enclosure
BTS DU enclosures for pico and small cells, which are front-, wall-, and pole-mountable.
Mini of 3 types: AC/DC type with an installed rectifier; DC type with an installed PDU; and an enclosure for a one-string battery.
The Mini includes an optional fan and filter depending on the heating value, and can assimilate a heating value of 1.1kW.
An indoor type of the FDD LTE DU cabinet with the same certification.
Categories
ODM
Total Space
18U
User Space
18U
Size (H X W X D)
1800 X 700 x 700mm
Weight
200kg(Without Battery)
Operating temperature
0℃ to +50℃, full power
Relative Humidity
5 ~ 95%RH
Earthquake
GR-63-Core, Zone 4
Ingress Protection
IP20
Battery Backup Time
4 Hours ( 4 Strings@190Ah )
Power distribution
-48VDC
Rectifier(PDU)
AC/DC, 7U LLVD, BLVD, Battery MCB Included, AC Distribution 1P+N+PE
DC power distribution with lighting protection
30kA, 8/20us (RRH) @normal
Power Consumption
3,950W@Typical
Indoor Enclosure : MMBS Single Indoor Enclosure
An indoor type of the FDD LTE Single cabinet with the same certification.
Categories
ODM
Total Space
12U
User Space
12U
Battery Space
1String
Size (H X W X D)
1800 X 700 x 700mm
Weight
210kg(Without Battery)
Operating temperature
0℃ to +50℃, full power
Relative Humidity
5 ~ 90%RH
Earthquake
GR-63-Core, Zone 4
Ingress Protection
IP20
Battery Backup Time
1 Hours ( 1 Strings@190Ah )
Power distribution
-48VDC
Rectifier(PDU)
AC/DC, 7U LLVD, BLVD, Battery MCB Included, AC Distribution 1P+N+PE
DC power distribution with lighting protection
30kA, 8/20us (RRH) @normal
Power Consumption
8,300W@Typical
Indoor Enclosure : MMBS Battery Indoor Enclosure
An indoor type of the FDD LTE Battery cabinet with the same certification.
Categories
ODM
Battery Space
4String
Size (H X W X D)
1800 X 700 x 700mm
Weight
140kg(Without Battery)
Operating temperature
0℃ to +50℃, full power
Relative Humidity
5 ~ 90%RH
Earthquake
GR-63-Core, Zone 4
Ingress Protection
IP20
Battery Backup Time
4 Hours ( 4 Strings@190Ah )
Power distribution
-48VDC
Indoor Enclosure : Small self-assembly Indoor Rack
An indoor rack for installation of self-assembly 19-inch DU (PDP). Possible installation in double stacks, and with the possible use as a cabinet type with an optional cover.
Categories
OEM
standards
19 inch
Size (H X W X D)
900 X 604 X 574 mm
Repeater Enclosure(etc,.)
STORM Enclosure
An enclosure to accommodate donors and power amplifiers for optical repeaters.
Categories
ODM
Total Space
36U
User Space
21U
Battery Space
5U
Size (H X W X D)
2000 X 650 x 925mm
Operating temperature
-30 ℃ to +50 ℃
Relative Humidity
10% ~ 90%
Earthquake
GR-63-Core, Zone 3
Ingress Protection
IP55
Cooling Capacity
1,800W
Battery Backup Time
4 Hours ( 4 Strings@190Ah )
Power distribution
+29VDC
DC power distribution with lighting protection
20kA, 8/20us
Power Consumption
2,185W ( Power AMP Built-In)
PDU (DC/DC)
1U, SDU 7 Port
Rectifier(PDU)
2U, Output 6 Port
STORM Hub Enclosure
An enclosure to accommodate donors for optical repeaters.
Categories
ODM
Total Space
36U
User Space
24U
Battery Space
5U
Size (H X W X D)
2000 X 650 x 925mm
Operating temperature
-30 ℃ to +50 ℃
Relative Humidity
10% ~ 90%
Earthquake
GR-63-Core, Zone 3
Ingress Protection
IP55
Cooling Capacity
1,335W
Battery Backup Time
4 Hours ( 4 Strings@190Ah )
Environment monitoring system (SCU)
Door Open(+Lamp), Temp
Power distribution
+29VDC
DC power distribution with lighting protection
20kA, 8/20us
Power Consumption
1,450W
PDU (DC/DC)
1U NTU 2 Slot , Donor 8 Port
Rectifier(PDU)
2U, Output 6 Port
NFOR Enclosure
A mini enclosure for cabinet-type repeaters that is different from the die-cast type for natural cooling.
Categories
ODM
Size (H X W X D)
1200 X 400 x 510mm
Operating temperature
-30℃ to +50℃ (Outdoor), -10℃ to +50℃ (Indoor)
Relative Humidity
10% ~ 90%
Earthquake
GR-63-Core, Zone 3
Ingress Protection
IP55
Cooling Capacity
1,400W ~ 1,600W
Smart Control Unit
Door&Lamp, Temp
Power distribution
+52VDC
DC power distribution with lighting protection
20kA, 8/20us
Power Consumption
2,200W
Network Enclosure(etc,.)
Cabinets (beacon racks) for airport navigation aid systems
Indoor cabinets to accommodate equipment for the safe take-off and landing of airplanes
Categories
OEM
Size (H X W X D)
1963 x 600 x 700mm
Weight
180.0kg(± 5.0kg)
Specifications
IEC 297, IEC 529 Standard, ISO 3834
PDU(PDP)
1U PDP
A slim PDP of 1U type to support a maximum of 9 RU systems. In compliance with EU standards.
Categories
ODM
Size (H X W X D)
43.6 x 482.6 x 200 mm
Operating temperature
-40℃ ~ +70℃
Relative Humidity
5% ~ 90%
Power input terminal
25 ㎟ max x 2 ports
Power output terminal
Wire cross section 6 ㎟ max
DC power capacity
256A max @ -48V DC
Power output port q'ty
25A x 10ea, 6A x 1ea
Circuit breaker
Hydraulic magnetic type
DC power distribution with lighting protection
20kA 8/20 us ( 30kA max )
A high-capacity PDU
A high-capacity PDPU for server systems, etc.
Categories
ODM
Size (H X W X D)
177 x 482.6 x 385 mm
Operating temperature
-5℃ ~ +70℃
Relative Humidity
5% ~ 90%
Power input terminal
120 ㎟ max, 2 ports
Power output terminal
Wire cross section 25 ㎟ max
DC power capacity
250A max @ -48V DC
Power output port q'ty
100A x 2ea, 15A x 2ea, 10A x 2ea
Circuit breaker
Hydraulic magnetic type
Smart Conrtol Unit
Global Stackable Power Outdoor Smart Control Unit
Categories
ODM
Case Size
204 x 140 x 34 mm
Case Material housing
SPCC
Weight
0.906Kg( Case : 0.706Kg, PBA : 0.2Kg )
Power supply
-38VDC ~ -57VDC( -53.7VDC @ Normal )
Power Consumption
Max 70W @ -53.7VDC
Supported Protocols
TCP/IP, UDP, TELNET, RS485, RS232
Ethernet interface.
4 Port, Physical Media 10 Base-T
Sensors monitor port
Door&Lamp, Fire
FAN control port
1 Port
HEATER control port
AC 220V 2KW Heater ON/OFF
TEMP Sensor Port
2 Port
Global Stackable Battery Outdoor Smart Control Unit
Categories
ODM
Case Size
180 x 78 x 36.2 mm
Case Material housing
SPCC
Weight
0.518Kg ( Case : 0.418Kg, PBA : 0.1Kg )
Power supply
-38VDC ~ -57VDC ( -53.7VDC @ Normal )
Power Consumption
Max 25W @ -53.7VDC
Supported Protocols
RS485
Sensors monitor port
Filter, Door&Lamp, Fire
FAN control port
1 Port
HEATER control port
AC 220V 2KW Heater ON/OFF
TEMP Sensor Port
2 Port
STORM Outdoor Smart Control Unit
Categories
ODM
Case Size
183 x 170 x 36.2 mm
Case Material housing
SPCC
Weight
1.04Kg( Case : 0.64Kg, PBA : 0.4Kg )
Power supply
+28.71VDC ~ +29.29VDC( +29.2VDC @ Normal )
Power Consumption
Max 25W @ +29.2VDC
Supported Protocols
RS485
Ethernet interface.
6 Port
Sensors monitor port
ACSPD alarm
TEMP Sensor Port
2 Port
STORM Hub Outdoor Smart Control Unit
Categories
ODM
Case Size
183 x 170 x 36.2 mm
Case Material housing
SPCC
Weight
0.45Kg( Case : 0.35Kg, PBA : 0.1Kg )
Power supply
Not Applicable
Power Consumption
Not Applicable
Supported Protocols
RS485
Sensors monitor port
2Port_Door&Lamp, Flood, SDU s/w
TEMP Sensor Port
3 Port
Shelf
DU Shelf Type 1
DU shelf for BS enclosures
Categories
OEM
standards
19 inch, 2U
Cooling Method
Direct Fan Cooling(FANM-C4)
Temperature Control
Installed with a Fan controller
DU Shelf Type 2
DU shelf for BS enclosures
Categories
OEM
standards
19 inch, 2U
Cooling Method
Direct Fan Cooling(FANM-C4A)
Temperature Control
Installed with a Fan controller
Repeater Digital Shelf
DU shelf for repeater enclosures. Two types of 3U and 4U.
Categories
OEM
standards
19 inch, 3U (4U)
Cooling Method
Direct Fan Cooling(DFU-FAN)
Temperature Control
Installed with a Fan controller
Fan Unit
DU Cooling Fan Module Type 1
DU shelf for Cooling Fan(Installed with a controller)
Categories
ODM
Size (H X W X D)
83.4 x 55.5 x 336.5mm
Operating temperature
-40℃ ~ +77 ℃
Relative Humidity
5% ~ 90%
Fan Spec
80 x 38, 4900 rpm, 3 pcs
Air Flow
205 CFM max
Power Consumption
24W @ 48VDC
Power rating
-48VDC
Communication
RS-232
DU Cooling Fan Module Type 2
DU shelf for Cooling Fan(Installed with a controller)
Categories
ODM
Size (H X W X D)
83.4 x 55.5 x 367mm
Weight
0.88 kg
Operating temperature
-40℃ ~ +80℃
Relative Humidity
5% ~ 90%
Fan Spec
80 x 38, 7500 rpm, 3 pcs
Air Flow
313.2 CFM max
Power Consumption
59.5W @ 48VDC
Power rating
-48VDC
Communication
I2C
SRU Cooling Fan Module Type 1
External outdoor cooling fan for a case-type RU system.
Categories
OEM
Size (H X W X D)
83.4 x 55.5 x 367 mm
Weight
0.88 kg
Operating temperature
-40℃ ~ +80℃
Relative Humidity
5% ~ 90%
Ingress Protection
CLASS IP55
Fan Spec
80 x 38, 6400 rpm, 2 pcs
Air Flow
158.8 CFM max
Power Consumption
10W @ 48VDC
Power rating
-48VDC
SRU Cooling Fan Module Type 2
External outdoor cooling fan for a case-type RU system.
Categories
OEM
Size (H X W X D)
81.4 x 439 x 98.9 mm
Weight
1 kg
Operating temperature
-40℃ ~ +80℃
Relative Humidity
5% ~ 90%
Ingress Protection
CLASS IP55
Fan Spec
80 x 38, 6400 rpm, 2 pcs
Air Flow
158.8 CFM max
Power Consumption
10W @ 48VDC
Power rating
-48VDC
19inch Shelf Fan
Consists of master and slave cooling fans for the server systems.
Categories
ODM
Size (H X W X D)
81.4 x 439 x 98.9 mm
Weight
6.5 kg
Operating temperature
-5℃ ~ +70℃
Relative Humidity
10% ~ 90%
Fan Spec
127 x 38, 6000 rpm, 6 pcs
Air Flow
1130 CFM max
Power Consumption
226W @ 48VDC
Power rating
-48VDC
Communication
RS-232
Heater Module
PTC Heater Module
An internal heater module installed in an outdoor cabinet
Categories
ODM
Case Size
165 x 160 x 95mm
Weight
1.2Kg( Case : 1.1Kg, PBA : 0.1Kg )
Power supply
AC220V, DC27V
Power Consumption
1,000W
Heat element
PTC
Heat Capacity
900W +5% ~ -10% @ airflow velocity fo 3.3m/s
Fan alarm port
1 port
Operating temperature
-40℃ to +80℃
Diecasting, M/C
RU(80W) SUB ASSY
An RU housing sub-assembly product that is made of die-cast AL
Categories
OEM
Size (H X W X D)
516 X 296 X 76 mm
Weight
6.3kg
Materials
AL Diecasting
2.1G Macro RRH Housing
An RU housing sub-assembly product that is made of die-cast AL
Categories
OEM
Size (H X W X D)
516 X 298 X 76 mm
Weight
4.5kg
Materials
AL Diecasting
OUTDOOR AP Housing
An AP housing sub-assembly product that is made of die-cast AL
Categories
OEM
Size (H X W)
Rear : 184 X 267 mm
Materials
AL Diecasting
RU Housing
An RU housing sub-assembly product that is made of a die-cast AL rear body, AL, and a fabrication cover
Categories
OEM
Size (H X W X D)
516 X 296 X 143 mm
Materials
Rear : AL Diecasting, Cover : AL processed
BPA
BPA
Backplane boards for various shelves
Categories
OEM
Enclosure Product
ESS Enclosure
ESS enclosures for homes and offices : 7.2/10.8 kWh Scalable ESS Outdoor Cabinet
Outdoor cabinets for the installation of batteries and controllers for ESS products
Categories
OEM
Size (H X W X D)
1512 x 850 x 400mm
Weight
60.0kg(± 5.0kg)
UPS Enclosure
Samsung SDI WIDE RACK(Model : WIDE 208S1P)
Indoor cabinets for the installation of batteries and controllers for ESS products
Categories
OEM
Size (H X W X D)
1700 x 1000 x 670mm
Weight
200.0kg(± 5.0kg)
Semiconductor Equipment
Core Semicon Equipment
Power Box Ass’y
Categories
OEM
Application
Semiconductor Etch & Deposition Equipment
Function
Power supply module
Frame Ass’y
Categories
OEM
Application
Semiconductor Etch & Deposition Equipment
Function
structural component of wafer processing Equipment